HSJ EnOcean One Hop Repeater

  • A repeater that receives EnOcean standard radio signals and transmits them once.

  • Start operation just by connecting the AC adapter

  • Reception and retransmission of all EnOcean standard radios without the need for pairing settings

Specification

ModelHSJ
Power Supply ※1AC Adapter (Micro USB connection 5V)
Transmission Method EnOcean
Communication Output1mW
Frequency928.35MHz
Radio Standard:(ARIB STD-T108)
Certification Number:003-13087
FunctionReceives and retransmits EnOcean telegrams.
At the time of retransmission, the relay flag is attached and transmitted.
If an EnOcean telegram with the relay flag is received, it will not be retransmitted.
AntennaBuilt-in whip antenna
Operating Environment 0℃~40℃
Use EnvironmentIndoor specification (No waterproof performance)

HYPM Particulate Matter Sensor (PM2.5)

  • Ideal for visualizing PM2.5 value

    ・Yellow sand
    ・Tobacco smoke
    ・Pollen
    ・House dust

  • Monitoring air at home is also possible

  • EnOcean transmission (Japan: 928.35MHz, Europe/China: 868.3 MHz, USA/Canada: 902.875MHz/Thailand:921.4 MHz)

Specification

ModelHYPM
Power supplyAC adaptor (Micro USB connection 5V)
Transmission interval1 min
Transmission distance30m ~ 120m
No. of sensorPM sensor 1 piece
Frequency
(EnOcean signal)
Japan: 928.35MHz (ARIB STD-T108) 1mW
Europe/China: 868.3 MHz 1mW
USA/Canada: 902.875 MHz 1mW
PM sensor specs Measurement range 1 ch : 0.3 ~1.0 μm
2 ch : 0.3 ~2.5 μm
3 ch : 0.3 ~4.0 μm
4 ch : 0.3 ~10.0 μm
Measurement range1 ch ~ 4 ch : 0 ~ 1000 μ g/m3
Resolution1 ch ~ 4 ch : 16bit (0.015μ g/m3)
Conversion formula1 ch ~ 4 ch : 16bit value x 1000 / 65535
Detection accuracy1 ch ~ 4 ch : detection amount 0 ~ 100 μ g/m3: ±10 μ g/m3
1 ch ~ 4 ch : detection amount 100 ~ 1000 μ g/m3: ±10% (at room temperature 25℃)
1 ch ~ 4 ch : detection amount 100 ~ 1000 μ g/m3: ±15% (under 10℃ or above 40℃)
Operating Temperature RangeTransmitter・ Sensor -10℃ ~ +60℃

HYCO Carbon dioxide (CO₂) Sensor

  • Ideal for visualizing carbon dioxide value

    ・Plant factory
    ・Theatres
    ・Meeting room

  • Built-in humidity sensor included

  • EnOcean signal (Japan: 928.35MHz, Europe/China: 868.3MHz, USA/Canada: 902.875 MHz/Thailand:921.4 MHz)

Specification

ModelHYCO
Power supplyAC adaptor (Micro USB connection 5V)
Transmission interval1 min
Transmission distance30m ~ 120m
No. of sensorCO2 sensor 1 piece
temperature and humidity sensor 1 channel
Frequency (EnOcean signal) Japan: 928.35MHz (ARIB STD-T108) 1mW
Europe/China: 868.3 MHz 1mW
USA/Canada: 902.875 MHz 1mW
CO2 sensor specs Measurement range: 0 ~ 40,000ppm
Resolution: 16bit (0.61 ppmLSB)
Conversion formula: 16bit value x 40000 / 65535
Detection accuracy: 400 ~ 10,000ppm: ± (30ppm+3%)
Temperature sensor specsMeasurement range: -40℃ ~ +70℃
Resolution: 16bit (0.0025%LSB)
Conversion formula: 16bit value x 175 / 65535
Detection accuracy: ±1.0℃ (at 25℃), ±3.0℃ (at -40℃ ~ +60℃)
Humidity sensor specsMeasurement range: 0 ~ 100%
Resolution: 16bit (0.0015% LSB)
Conversion formula: 16bit value x 100 / 65535
Detection accuracy: ±2.0% (at 25℃), ±4.0% (at 0℃ ~ +60℃)
Operating Temperature RangeTransmitter: -10℃ ~ +60℃
Sensor: 0℃ ~ +50℃

HYHU-1 Thermometer and humidity sensor

  • Measurement range: Temperature -20℃ ~ +60℃, Humidity 0 ~ 100% RH

  • Transmission Interval 10 min

  • Hybrid power: solar and long-life coin battery (5 years)

  • Waterproof type

  • Self-powered EnOcean transmission

  • Low-cost type

  • Transmistter and sensor together in a single unit

Specification

ModelHYHU-1
Power supplyCoin battery (CR2032) + Solar panel as backup power
Transmission interval 10 min
Transmission distance30m~120m
No. of sensorThermometer and humidity sensor 1 piece
Frequency (EnOcean signal) Japan: 928.35MHz (ARIB STD-T108) 1mW
Europe/China: 868.3 MHz 1mW
USA/Canada: 902.875 MHz 1mW
Thermometer specsTemperature range -20℃ ~ +60℃
Temperature accuracy ±1.0℃ (at 25℃)
Temperature accuracy ±3.0℃ (at -20℃~+60℃)
Temperature resolution 0.0025℃%
Humidity sensor specsHumidity range 0% ~ 100%
Humidity accuracy ±2% (at 25℃)
Humidity accuracy ±4% (at 0℃~+60℃)
Humidity resolution 0.0015%
Operating Temperature Range -20℃~ +60℃

HYHQ Temperature Sensor (Transmitter)

  • To use with high precision temperature sensor, Pt1000Ω class A

  • Self-powered EnOcean transmission

  • Wide range of measurement -40℃~+250℃

  • Can connect to backup battery

  • Hybrid power between solar panel and coin battery

Specification

ModelHYHQ
Power supplyHybrid power of solar panel and coin battery
Communication method4 selectable interval: 5 min※, 10min, 30min, 60min


Installing in the place with lights is required, please contact us in the case of transmission interval less than 10 min.
Transmission distance30m~120m
No. of temperature sensor connectionMax. 2ch (connectors)
Frequency (EnOcean signal) Japan: 928.35MHz (ARIB STD-T108) 1mW
Europe/China: 868.3 MHz 1mW
USA/Canada: 902.875 MHz 1mW
Temperature sensorSensor: Pt1000Ω class A 3m
Range : -40℃ ~ +250℃
Accuracy: ±0.5℃ (at 0℃)
Accuracy: ±0.5℃ (at 0℃)
Resolution: 0.05℃
Operating Temperature Range0℃~40℃(Transmitter)

HYJ Temperature sensor transmitter

  • Driven by solar battery, no electricity needed

  • To monitor temperature data from distance

  • Data can be converted to electronic data

  • Max. 120m of transmission distance of temperature data

  • Connecting to switch type of sensor is also possible

Specification

ModelHYJ
Power supplySolar battery
Transmission methodTypeA:60 sec interval、TypeB:600 sec interval
Required lightTypeA:>540 【lx】、TypeB:>65【lx】
Operation in the darknessTypeA:24 hours after full charge、TypeB:50 hours after full charge
Frequency (EnOcean signal)Japan: 928.35MHz (ARIB STD-T108) 1mW
Europe/China: 868.3 MHz 1mW
USA/Canada: 902.875 MHz 1mW
Temperature sensorSensor: Pt100Ω class B (or equivalent) 3m
Range : -30℃ ~ +120℃
Accuracy: ±1.5℃ (at 0℃)
Operating Temperature Range0℃~40℃(Transmitter)

Pt-1000A Temperature sensor

  • To use with wireless temperature sensor transmission HYHQ

  • Connector to connect to HYHQ included

  • Using high precision Pt1000Ω class A

Specification

Model型式Pt1000A
TypePt1000Ω class A 3wires
Operating Temperature Range50℃ ~ 260℃
Wire cover materialFEP
Heat resistance temperature of wire260℃
Wire lengthStandard 3m
Wire tip materialSUS
Tip shapeφ3.2×40 cylinder
Main application・Internal temperature of metal block etc
・Sensor and be temporarily wetted but must not be placed in any liquid

Pt-100B Temperature sensor

  • Can connect to wireless temperature sensor transmitter HYJ

  • Customizable depending on your application

Specification

ModelsPt100B-101Pt100B-201Pt100B-301
TypePt100Ω Class B 3 wires
Operating Temperature Range-40℃~+130℃
Wire cover materialFEP
Heat resistance temperature of wire200℃
Wire lengthStandard 3m
Wire tip materialSUSAluminumFluorine resin
Tip shapeφ3×25 cylinderFlat shape with M3 holeApprox.φ3×30
Main applicationInternal temperature of metal block etc
Sensor and be temporarily wetted but
must not be placed in any liquid
Surface temperatureAir temperature

※ Specifications are subject to change without notice

WUSB400J EnOcean Receiver

  • Easy-to-display program included

  • Connect to USB port of PC

  • Multiples data sources can be taken in by just 1 receiver※1

    ※1 Developed program specialized in displaying multiple data required